大空间两种气流组织夏季热环境及其能耗实验研究
Experimental study on the thermal environment and energy consumption of a large space under two different air supply modes of air conditioning in summer
投稿时间:2015-06-12  
DOI:10.13259/j.cnki.eri.2016.02.004
中文关键词:  喷口送风  柱状下送风  大空间  室内热环境  供冷量
英文关键词:nozzle air supply  column air supply at lower side  large space  indoor thermal environment  cooling load
基金项目:国家自然科学基金资助项目(51278302);沪江基金资助项目(D14003)
作者单位E-mail
陈帅 上海理工大学 环境与建筑学院, 上海 200093  
黄晨 上海理工大学 环境与建筑学院, 上海 200093 hcyhyywj@163.com 
张亚林 上海理工大学 环境与建筑学院, 上海 200093  
刘雷明 上海理工大学 环境与建筑学院, 上海 200093  
刘俊 上海理工大学 环境与建筑学院, 上海 200093  
刘昊儒 上海理工大学 环境与建筑学院, 上海 200093  
摘要点击次数: 3929
全文下载次数: 2645
中文摘要:
      以某大空间实验基地为研究对象,针对喷口送风和柱状下送风两种分层空调的热环境及供冷量进行了实测研究。研究结果表明:因喷口送风空调区较大,在夏季室外气象参数基本相同的两种室外气象条件下,喷口送风空调系统供冷量比柱状下送风空调系统的供冷量分别高出20.8%、24.4%,且喷口送风空调系统抗干扰能力较柱状下送风强;喷口送风时工作区温度均匀性好于柱状下送风,头足温差较小,但其工作区风速超过标准,而柱状下送风时工作区风速则符合环境设计要求;两种不同送风量下喷口送风时吹风感指数分别为15.64%、11.23%,而柱状下送风时吹风感指数分别为4.17%、2.40%,柱状下送风要明显优于喷口送风。故从节能及热舒适性角度综合考虑,单侧回风的大空间建筑应尽可能采用柱状下送风分层空调,而对于干扰比较大,空调场地较小,无法布置柱状下送风口的场合,则选取喷口送风较好。
英文摘要:
      The thermal environment and cooling load in a large space were studied in summer under stratified air conditioning with two air supply modes of nozzle air supply at middle side and column air supply at lower side.The results showed that the total cooling load of the former under two different outdoor weather conditions in summer was 20.8% and 24.4% higher than that of the latter, due to the larger air-conditioned area of the former.Furthermore, the anti-jamming capability of air conditioning system with nozzle air supply was better.The temperature uniformity in the workplace of the former was better than that of the latter.The temperature difference between the head and feet was smaller.But the air velocity in the air-conditioning zone of the former has exceeded the standards while the latter could meet the design requirements of the environment.The wind-being index PD in the mode of nozzle air supply was 15.64% and 11.23% while the other one was 4.17% and 2.40% under two different air supply flow.Therefore, the column air supply mode at lower side was better than the nozzle air-supply mode in this aspect.The conclusions could be drawn in terms of energy efficiency and thermal comfort that the air-conditioning system in a large space building with unilateral return air should use the column air supply mode at lower side.And it was better to use the nozzle air supply mode in the building where the interference was large or the column outlet couldn't be arranged at lower side.