| Based on an evaluation of the available resources such as geothermal energy, data center waste heat, natural gas, electricity, and heat grid around a science and technology industrial park in Beijing, along with a comprehensive analysis of building cooling and heating loads, three schemes were proposed to meet the full heating demand: a hybrid system combining ground source heat pumps, air source heat pumps, and waste heat heat pumps; data center waste heat recovery; and a chiller integrated with gas boiler system. The advantages and disadvantages of each scheme were analyzed. The operating principle and equipment configuration of the hybrid system were presented, as well as the calculation of its economic and environmental indicators, including operating costs, internal rate of return, payback period, coal savings, electricity savings, carbon emission reduction, and pollutant emission reduction. The results show that the hybrid system achieves an energy consumption index of approximately 4.22 kgce/m2, corresponding to a reduction of 752.53 t in energy consumption, 2 001.73 t in CO2 emissions, 17.01 t in SO2 emissions, and 14.81 t in NOx emissions, demonstrating favorable energy conservation, environmental protection, and economic benefits. |